0,6/1KV - AL/PVC - 1 Core (AV) Power Cable Type Designation Code Cable Code: NAY-O 1 x ### sqmm CM 0.6/1 kV NA: Aluminum conductor | Y: PVC | #### sqmm: Conductor nominal area | CM: Circular compacted stranded (Conductor shape)
Classification • Rated voltage (Uo/U): 0.6/1kV • Max. conductor temperature in normal operation: 70ºC • Max. conductor temperature in short-circuit for 5s max duration: 160ºC
Nominal area
Structure
Diameter
Thickness of insulation
Overall diameter
DC resistance at 20 0C
Approx. weight
Test voltage 50Hz-5min
(mm2)
(N0 x mm)
(mm)
(Ω/Km)
(Kg/Km)
(kVr.m.s)
16
CC
4.9
1.0
6.9
1.910
82
3.5
25
6.1
1.2
8.5
1.200
126
35
7.1
9.5
0.868
163
50
8.2
1.4
10.9
0.641
221
70
9.8
12.5
0.443
293
95
11.5
1.6
14.7
0.320
401
120
12.9
16.1
0.253
485
150
14.4
1.8
17.9
0.206
597
185
2.0
20.0
0.164
746
240
18.4
2.2
22.8
0.125
964
300
20.7
2.4
25.4
0.100
1,199
400
23.5
2.6
28.6
0.0778
1,514
500
26.5
2.8
32.0
0.0605
1,887
630
30.6
36.2
0.0469
2,359