8.7/15 (17.5)KV - AL/XLPE/PVC - 1 Core (AXV/S) Power Cable

8.7/15 (17.5)KV - AL/XLPE/PVC - 3 Cores (AXV/S) Power Cable

Type Designation Code

Cable Code: NA2XSY-O 3 x ### sqmm CM 8.7/15 kV
NA: Aluminium conductor | 2X: XLPE | S: Copper tape | Y: PVC | #### sqmm: Conductor nominal area | CM: Circular compacted stranded (Conductor shape)

Specifications


8.7/15 kV AL/XLPE/PVC - 1 Core (AXV/S) Power Cable
Power cable, 3 core, aluminium conductor, XLPE insulated, PVC sheathed.

Structure
    (1). Conductor: Aluminium conductor class2, circular compacted, complied to IEC 60228
    (2). Conductor screen: Semi - conductive compound
    (3). Insulation: Cross - linked polyethylen (XLPE)
                     Color: natural color
    (4). Insulation screen: Semi - conductive compound
    (5). Color tape: Color tapes lie between insulation screen and copper screen
    (6). Metallic screen: Copper tape
    (7). Inner sheath: Filler PP, binder tape, Polyvinyl chloride (PVC)
    (8). Outer sheath: Polyvinyl chloride (PVC)
                     Color: Black  or other color

Markings
#### M - NGOC LAN CABLE - YYYY - AXV/S 3x ”SIZE”  mm² - 8.7/15 (17.5)KV
Standards
IEC 60502-2; IEC 60228 or equivalent
Application
Used for overhead power transmission lines and power distribution,...

Classification
    • Rated voltage Uo/U(Um): 8.7/15 (17.5)KV
    • Max. conductor temperature in normal use: 90ºC

Characteristics

Nominal area

Diameter
of core

Thickness of insulation

Thickness of sheath

Overall diameter

DC resistance
at 200C

Approx.
weight

(mm2)

(mm)

(mm)

(mm)

(mm)

(Ω/Km)

(Kg/Km)

35

7.1

4.5

1.7

22.9

0.868

590

50

8.2

4.5

1.7

24.0

0.641

660

70

9.8

4.5

1.8

25.8

0.443

770

95

11.5

4.5

1.8

27.5

0.320

890

120

12.9

4.5

1.9

29.1

0.253

1,010

150

14.4

4.5

1.9

30.6

0.206

1,120

185

16.1

4.5

2.0

32.5

0.164

1,280

240

18.4

4.5

2.1

35.0

0.125

1,520

300

20.7

4.5

2.1

37.3

0.100

1,750

400

23.5

4.5

2.2

40.3

0.0778

2,090