8.7/15 (17.5)KV - AC.WB/XLPE/PVC - (ACXV/WB) Power Cable

8.7/15 (17.5)KV - AC.WB/XLPE/PVC -  (ACXV/WB) Power Cable

Power cable, single-core, aluminium conductor steel reinforced, XLPE insulated, PVC sheathed

Specifications


8.7/15 (17.5) kV  AC.WB/XLPE/PVC -  (ACXV/WB) Power Cable
Power cable, single-core, aluminium conductor steel reinforced, XLPE insulated, PVC sheathed
Structure
    (1). Conductor:
                     Steel part: Zinc- coated steel wires, one wire or multi-wires concentric stranded
                     Aluminium part: Hard drawn aluminium wires, concentric stranded
    (2). Insulation:Cross-linked polyethylen (XLPE)
    (3). Outer sheath:Black polyvinyl cloride (PVC)   
Markings
#### M - NGOC LAN CABLE - YYYY - AC.WB/XLPE/PVC 1x ”SIZE” mm² -  8.7/15 (17.5)KV
Standards
 IEC 60502-2 – TCVN 5935:1995; TCVN 5064:1994/SD:1995 or equivalent.
Application
Used for overhead power transmission lines and power distribution

Classification
    • Rated voltage Uo/U(Um): 8.7/15(17.5) KV
    • Max. conductor temperature in normal operation: 90ºC

Characteristics

Nominal area

Aluminium

Steel

Diameter of core

Thickness of
insulation

Thickness
of sheath

Overall
diameter

DC resistance at 200C

Min.
breaking
load

Approx.
weight

(mm2)

(N0 x mm)

(N0 x mm)

(mm)

(mm)

(mm)

(mm)

(Ω/km)

(N)

(Kg/Km)

50/ 8

6 x 3.20

1 x 3.20

9.60

4.5

1.6

21.8

0.5951

17,112

549

70/ 11

6 x 3.80

1 x 3.80

11.40

4.5

1.7

23.8

0.4218

24,130

675

95/ 16

6 x 4.50

1 x 4.50

13.50

4.5

1.7

30.9

0.3007

33,369

841

120/ 19

26 x 2.40

7 x 1.85

15.15

4.5

1.8

27.8

0.2440

41,521

973

150/ 19

24 x 2.80

7 x 1.85

16.75

4.5

1.9

29.6

0.2046

46,307

1,101

185/ 24

24 x 3.15

7 x 2.10

18.90

4.5

2.0

31.9

0.1540

58,075

1,317

240/ 32

24 x 3.60

7 x 2.40

21.60

4.5

2.0

34.6

0.1182

75,050

1,613