18/30 (36)KV - AL/WB/XLPE/PVC - 1 Core (AXV/WB) Power Cable

18/30 (36)KV - AL/WB/XLPE/PVC - 1 Core (AXV/WB) Power Cable

Type Designation Code

Cable Code: NA2XY-O 1 x #### sqmm RM 18/30 (36) kV
NA: Aluminium conductor | 2X: XLPE | Y: PVC | #### sqmm: Conductor nominal area | RM: Round stranded (Conductor shape)

Specifications

18/30 (36) kV Al/WB/XLPE/PVC - 1 Core (AXV/WB) Power Cable
Power cable, single-core, aluminium conductor, XLPE insulated
Structure
    (1). Conductor: Aluminium conductor class2, complied to IEC 60228
    (2). Insulation: Cross-linked polyethylen (XLPE)
    (3). Outer sheath: Polyvinyl cloride (PVC)          
Markings
#### M - NGOC LAN CABLE - YYYY - AXV/WB 1x ”SIZE” mm² - 18/30 (36)KV
Standards
 IEC 60502-2; IEC 60228 or equivalent
Application
Used for overhead power transmission lines and power distribution,..

Classification
    • Rated voltage Uo/U(Um): 18/30 (36)KV
    • Max. conductor temperature in normal operation: 90ºC

Characteristics

Nominal
area

Structure

Diameter of core

Thickness of insulation

Thickness of sheath

Overall diameter

DC resistance
at 200C

Approx.
weight

(mm2)

(N0 x mm)

(mm)

(mm)

(mm)

(mm)

(Ω/Km)

(Kg/Km)

35

7 x 2.52

7.56

8.0

1.8

27.3

0.868

706

50

19 x 1.80

9.00

8.0

1.9

28.8

0.641

810

70

19 x 2.14

10.70

8.0

1.9

31.5

0.443

923

95

19 x 2.52

12.60

8.0

2.0

32.4

0.320

1,076

120

37 x 2.03

14.21

8.0

2.1

34.2

0.253

1,217

150

37 x 2.25

15.75

8.0

2.1

36.0

0.206

1,377

185

37 x 2.52

17.64

8.0

2.2

38.0

0.164

1,534

240

61 x 2.25

20.25

8.0

2.3

40.9

0.125

1,836

300

61 x 2.52

22.68

8.0

2.4

43.5

0.100

2,084