450/750V - CU/PVC/PVC - 2 cores (CVVm) Building Wire & Cable

450/750V - CU/PVC/PVC -  2 cores (CVVm) Building Wire & Cable

Type Designation Code

Cable Code: NYY-O 2 x #### sqmm FX 450/750 V
N: Copper conductor | Y: PVC | Y: PVC | #### sqmm: Copper conductor | FX: Flexible (Conductor shape)

Specifications


450/750 V CU/PVC/PVC -  2 cores (CVVm) Building Wire & Cable
Building wire & cable, conductor annealed copper wires, bunched class 5, insulation PVC, sheath PVC

Structure
    (1). Conductor: Annealed copper wires, bunched class 5, complied to IEC 60228
    (2). Insulation: Polyvinyl chloride (PVC)
                   Color: red, black or other colours
    (3). Outer sheath: Polyvinyl chloride (PVC)
                   Color: Black or other colours 

Markings
#### M - NGOC LAN CABLE - YYYY - VVCm 2x ”SIZE” mm² - 450/750V
Standards
IEC 60228; IEC 60227 or equivalent
Application
Used for lighting systems, device in building

Classification
    • Rated voltage (Uo/U): 450/750V
    • Max. conductor temperature in normal operation: 70ºC  

Characteristics

Type

Structure

Insulation diameter

Diameter sheath

Approx.
weight

DC resistance
 at 20oC

Permissible curent

(mm2)

(mm)

(mm)

(mm)

(kg/km)

(Ω/km)

(A)

VVCm 2x0.5

2x16/0.20

0.7

1.2

35

39.0

5.3

VVCm 2x1.0

2x32/0.02

0.7

1.2

40

19.5

10.0

VVCm 2x1.5

2x30/0.25

0.7

1.2

48

13.3

15.0

VVCm 2x2.5

2x50/0.25

0.8

1.2

56

7.98

25.0

VVCm 2x4.0

2x80/0.25

0.8

1.2

75

4.95

35.0

VVCm 2x6.0

2x3x40/0.25

0.8

1.2

110

3.30

43.0

VVCm 2x10

2x5x40/0.25

1.0

1.4

205

1.91

60.0