0,6/1KV - AL/XLPE - 4 Cores aerial bundled cable (ABC) Type Designation Code Cable Code: NA2X-O 3 x #### sqmm CM 0.6/1kV NA: Aluminium conductor | 2X: XLPE | #### sqmm: Conductor nominal area | CM: Circular compacted stranded (Conductor shape)
Structure (1). Conductor: Stranded compacted circular aluminium (2). Insulation: Cross-linked polyethylen (XLPE) - UV Protection
Cable identification By ribs on black color insulation For 3 cores cable • Phase 1: 1 rib • Phase 2: 2 ribs • Neutral core: not less than 10 ribs (Table 1)or no rib Table1:
Nominal area (mm2)
16
25
35
50
70
95
120
150
Number ribs
10
12
14
18
20
22
24
Classification • Rated voltage (Uo/U): 0.6/1kV • Max. conductor temperature in normal operation: 90ºC • Max. conductor temperature in short-circuit for 5s max duration: 250ºC
Nominal area
Structure
Diameter of conductor
Thickness of insulation
Maximum dimeter of core
Cable dimeter
DC resistance at 20 0C
Approx. weight
(mm2)
(N0 x mm)
(mm)
(Ω/km)
(kg/km)
7/CC
4.7
1.3
7.3
17.6
1.910
272
6.0
9.2
20.7
1.200
398
7.0
10.3
23.3
0.868
519
8.2
1.5
11.9
27.1
0.641
728
19/CC
9.9
13.6
31.1
0.443
958
11.6
1.7
15.9
36.3
0.320
1,311
13.2
17.5
40.1
0.253
1,581
14.5
18.9
43.3
0.206
1,985