0,6/1KV - AL/XLPE - 4 Cores aerial bundled cable (ABC)

0,6/1KV - AL/XLPE - 4 Cores aerial bundled cable (ABC)

Type Designation Code

Cable Code: NA2X-O 3 x ####  sqmm CM 0.6/1kV
NA: Aluminium conductor | 2X: XLPE | #### sqmm: Conductor nominal area | CM: Circular compacted stranded (Conductor shape)

Specifications



Low voltage aerial bunched cable, 4 cores, aluminium conductor, XLPE insulated

Structure
    (1). Conductor: Stranded compacted circular aluminium
    (2). Insulation: Cross-linked polyethylen (XLPE) - UV Protection          

Markings
#### M - NGOC LAN CABLE - YYYY - LV ABC 4x ”SIZE” mm² - 0.6/1KV  
Standards
IEC 60228, IEC 60502-1 or equivalent
Application
Laid on cable ladder, tray, in duct in a thermal insulated wall, on a wall or spaced from wall, on the dry and closed cable trench in workshops, building, from source to machine or device, in duct in the ground.

Cable identification
By ribs on black color insulation
For 3 cores cable
• Phase 1: 1 rib
• Phase 2: 2 ribs
• Neutral core: not less than 10 ribs (Table 1)or no rib

Table1:

Nominal area (mm2)

16

25

35

50

70

95

120

150

Number ribs

10

12

14

16

18

20

22

24

Classification
    • Rated voltage (Uo/U): 0.6/1kV
    • Max. conductor temperature in normal operation: 90ºC
    • Max. conductor temperature in short-circuit for 5s max duration: 250ºC

Characteristics

Nominal area

Structure

Diameter of conductor

Thickness
of insulation

Maximum
dimeter of core

Cable
dimeter

DC resistance
at 20 0C

Approx. weight

(mm2)

(N0 x mm)

(mm)

(mm)

(mm)

(mm)

(Ω/km)

(kg/km)

16

7/CC

4.7

1.3

7.3

17.6

1.910

272

25

7/CC

6.0

1.3

9.2

20.7

1.200

398

35

7/CC

7.0

1.3

10.3

23.3

0.868

519

50

7/CC

8.2

1.5

11.9

27.1

0.641

728

70

19/CC

9.9

1.5

13.6

31.1

0.443

958

95

19/CC

11.6

1.7

15.9

36.3

0.320

1,311

120

19/CC

13.2

1.7

17.5

40.1

0.253

1,581

150

19/CC

14.5

1.7

18.9

43.3

0.206

1,985